Wall Tie Design Considerations

Key criteria for specifying masonry wall ties: wall construction and substrate, tie type selection to PD 6697:2019, design actions and tie capacity, spacing, edges and openings, movement joints, embedment and installation checks. Based on the Keyfix wall tie brochure.

Guidance only. Project design must confirm design actions, tie resistance, safety factors, substrate, exposure, applicable standards and manufacturer data.

01 — Technical Criteria

Technical Criteria

Wall tie design begins with the wall construction, the substrate the tie fixes into and the tie type selected to PD 6697:2019. These inputs must be confirmed for each project before spacing is considered.

Wall Construction & Substrate

  • Identify the outer leaf and inner leaf or backing structure (masonry, concrete or frame).
  • Confirm the cavity width, as this governs tie length and embedment.
  • Confirm the substrate material and condition the tie will be fixed into.
  • Record the exposure conditions for the project location.

PD 6697:2019 Tie Selection

  • Select the tie type in accordance with PD 6697:2019 for the wall construction and building use.
  • Confirm the declared tie capacity (Tc) from manufacturer data for the chosen product.
  • Check tie suitability for the cavity width, substrate and exposure.
  • Project design must confirm the standard, tie resistance and applicable factors.

02. DESIGN ACTIONS & TIE CAPACITY — KEYFIX BROCHURE P.16

Design Calculations

W = Wt × Dt; Nt ≥ W/Tc

Nt = 1,000,000 / (h × v) therefore v = 1,000,000 / (Nt × h)

W = design load per m² · Wt = load per tie · Dt = tie density (ties/m²) · Tc = tie capacity · Nt = number of ties per m² · h = horizontal spacing (mm) · v = vertical spacing (mm)

Worked example (illustrative)

Important: this example omits safety factors and is illustrative only — it is not a project design. Project design must confirm design actions, tie resistance, partial factors, substrate, exposure, applicable standards and current manufacturer data.

Load per tie, Wt

2,000 N

Tie density, Dt

3.7 ties/m²

W = Wt × Dt

7,400 N/m²

Tie capacity, Tc

1,580 N

Nt ≥ W/Tc

≥ 4.7 ties/m²

Horizontal spacing, h

600 mm

v = 1,000,000 / (Nt × h)

≈ 355 mm (calculated)

Selected vertical spacing

300 mm — to suit 75 mm brick courses

03 — Brochure p.16 calculation

Worked Example

The Keyfix brochure (p.16) sets out a baseline method for establishing tie spacing from the design action on the wall, the tie density and the tie capacity. The governing relationships are W = Wt × Dt, Nt ≥ W/Tc and Nt = 1,000,000/(h × v), therefore v = 1,000,000/(Nt × h).

Project design must confirm design actions, tie resistance, partial safety factors, substrate, exposure, applicable standards and current manufacturer data.

Step-by-step calculation

  1. Tie load input: Wt = 2,000 N
  2. Tie density: Dt = 3.7 ties/m²
  3. Design action: W = Wt × Dt = 2,000 × 3.7 = 7,400 N/m²
  4. Tie capacity: Tc = 1,580 N
  5. Required ties: Nt ≥ W/Tc = 7,400/1,580 ≈ 4.7 ties/m²
  6. Vertical spacing: h = 600 mm
  7. Calculated spacing: v = 1,000,000/(Nt × h) = 1,000,000/(4.7 × 600) ≈ 355 mm
  8. Selected spacing: v = 300 mm, to suit 75 mm brick courses

This example omits safety factors and is illustrative only. It is not a project design and must not be used for specification.

Spacing references from the Keyfix brochure (p.15)

These are brochure reference arrangements, not universal design instructions. Where both masonry leaves are at least 90 mm thick: minimum 2.5 ties/m² at 900 mm horizontal × 450 mm vertical centres, evenly distributed and staggered. For channel ties to a steel frame: typical 600 mm horizontal spacing and 600 mm vertical centres, 3.7 ties/m², evenly distributed and staggered.

For timber frame ties: 4.4 ties/m² at 600 mm horizontal × 375 mm vertical centres. At vulnerable unbonded edges: additional ties at 300 mm vertical centres and no more than 225 mm from the edge. Across opening heads and sills: ties 225 mm from the edge and no more than 450 mm horizontal centres. At vertical movement joints: ties no more than 225 mm from the joint and no more than 300 mm vertically.

Large buildings, coastal or exposed sites, unusual layouts, design actions and product resistances can require project-specific calculation and increased provision. Project design must confirm the applicable actions, tie resistance, factors, substrate, exposure, standards and manufacturer data.

04. STRUCTURAL INTEGRATION

Vulnerable Areas and Movement Joints

Baseline tie spacing alone does not address every location in a cavity wall. Additional ties are typically considered where the outer leaf is interrupted or free, as outlined in the Keyfix brochure and PD 6697:2019.

Openings

Around window and door openings the outer leaf loses continuity. Additional ties at closer centres are placed along reveals, heads and sills, within the distance from the opening edge given by the project design and referenced standard.

Unbonded Edges

Free or unbonded edges, such as the tops of walls, gables and vertical edges not bonded to returns, require supplementary ties so the outer leaf is restrained along its full perimeter. Spacing must be confirmed in the project design.

Movement Joints

A movement joint creates an unbonded edge on each side. Additional ties are placed either side of the joint to restrain both panel edges while still allowing the intended movement to occur.

Guidance only. Tie positions, edge distances and spacings must be confirmed by the project designer against design actions, tie resistance, factors, substrate, exposure, current standards and manufacturer data.

05 — INSTALLATION

Installation Standards

Embedment, tie length and site installation must be confirmed against the project design and the manufacturer's published data. The points below summarise items to check; they are not a substitute for a project-specific specification.

Embedment and tie length

  • Select tie length from the cavity width, the substrate and the embedment required in each leaf.
  • Confirm the minimum embedment into the mortar bed and into the substrate from manufacturer data.
  • Allow for tolerances in cavity width so the specified embedment is achieved on site.

Installation checks

  • Tie type and length match the approved specification.
  • Horizontal and vertical spacing follow the design, including additional ties at openings, unbonded edges and movement joints.
  • Ties are bedded to the specified embedment and not bent or damaged.
  • Ties are installed in accordance with the manufacturer's instructions.

Project design must confirm actions, tie resistance, factors, substrate, exposure, applicable standards and manufacturer data.

06 — TECHNICAL REVIEW

Project Review Checklist

To support a technical review of a wall tie specification, please provide the following project information:

  • Wall construction, cavity width and substrate (inner leaf material and condition)
  • Outer leaf masonry type and brick course height
  • Building height, location and exposure conditions
  • Design actions (wind load) confirmed for the project
  • Proposed tie type and category with reference to PD 6697:2019
  • Manufacturer tie capacity data for the selected tie and substrate
  • Openings, unbonded edges and movement joint locations
  • Required embedment and tie length
  • Applicable standards and any project-specific requirements
Design caveats

The guidance and worked example on this page are illustrative only and do not constitute a project design. The example omits safety factors. Project design must confirm design actions, tie resistance, partial safety factors, substrate, exposure, applicable standards and current manufacturer data.